防火卷帘门广泛应用于工业与民用建筑的防火隔断区,能有效地阻止火势蔓延,保障生命财产,是现代建筑中不可缺少的防火设施。那么防火卷帘门使用时的控制要求有什么?济南卷帘门厂家为您讲解。
The fireproof rolling shutter door is widely used in the fire partition area of industrial and civil buildings, which can effectively prevent the spread of fire and ensure the safety of life and property. It is an indispensable fire prevention facility in modern buildings. What are the control requirements for the use of fire rolling shutter doors? Jinan roller shutter door manufacturer explains to you.
1.防火卷帘的升降应由防火卷帘控制器控制。
1. The lifting of fire shutter shall be controlled by fire shutter controller.
2.疏散通道上设置的防火卷帘的联动控制设计,应符合下列规定:
2. The linkage control design of the fire shutter set on the evacuation exit shall meet the following requirements:
1)联动控制方式,防火分区内任两只独立的感烟火灾探测器或任一只专门用于联动防火卷帘的感烟火灾探测器的报警信号应联动控制防火卷帘下降距楼板面1.8m处;任一只专门用于联动防火卷帘的感温火灾探测器的报警信号应联动控制防火卷帘下降到楼板面;在卷帘的任一侧距卷帘纵深0.5m~5m内应设置不少于2只专门用于联动防火卷帘的感温火灾探测器。
1) Linkage control mode: the alarm signal of any two independent smoke fire detectors or any smoke fire detector specially used for linkage fire shutter in the fire compartment shall be linked to control the fire shutter to descend to 1.8m from the floor; The alarm signal of any temperature fire detector specially used for linkage fire shutter shall be linked to control the fire shutter to descend to the floor; At least 2 heat fire detectors specially used for linkage fire shutter shall be set within 0.5m~5m from either side of the shutter to the depth of the shutter.
2)手动控制方式,应由防火卷帘两侧设置的手动控制按钮控制防火卷帘的升降。
2) In manual control mode, the lifting and lowering of the fire shutter shall be controlled by the manual control buttons set at both sides of the fire shutter.
说明:设置在疏散通道上的防火卷帘,主要用于防烟、人员疏散和防火分隔,因此需要两步降落方式。
Note: The fire roller shutter set on the evacuation exit is mainly used for smoke prevention, personnel evacuation and fire separation, so it requires a two-step landing mode.
防火分区内的任两只感烟探测器或任一只专门用于联动防火卷帘的感烟火灾探测器的报警信号联动控制防火卷帘下降距楼板面1.8m处,是为保障防火卷帘能及时动作,以起到防烟作用,避免烟雾经此扩散,既起到防烟作用又可保证人员疏散。
The alarm signal of any two smoke detectors in the fire compartment or any smoke fire detector specially used for linkage of the fire shutter controls the fire shutter to drop to 1.8m from the floor. This is to ensure that the fire shutter can act in time to prevent smoke and prevent smoke from spreading through this process, which can not only prevent smoke but also ensure personnel evacuation.
济南卷帘门
感温火灾探测器动作表示火已蔓延到该处,此时人员已不可能从此逃生,因此,防火卷帘下降到底,起到防火分隔作用。
The action of the temperature sensing fire detector indicates that the fire has spread to this place. At this time, it is impossible for people to escape from this place. Therefore, the fire shutter is lowered to the bottom to play the role of fire separation.
3.非疏散通道上设置的防火卷帘的联动控制设计,应符合下列规定:
3. The linkage control design of the fire shutter set on the non evacuation exit shall meet the following requirements:
1)联动控制方式,应由防火卷帘所在防火分区内任两只独立的火灾探测器的报警信号,作为防火卷帘下降的联动触发信号,并应联动控制防火卷帘直接下降到楼板面。
1) In linkage control mode, the alarm signal of any two independent fire detectors in the fire compartment where the fire shutter is located shall be used as the linkage trigger signal for the fire shutter to descend, and the fire shutter shall be controlled to descend directly to the floor.
2)手动控制方式,应由防火卷帘两侧设置的手动控制按钮控制防火卷帘的升降,并应能在消防控制室内的消防联动控制器上手动控制防火卷帘的降落。
2) For manual control mode, the manual control buttons set at both sides of the fire shutter shall control the lifting and lowering of the fire shutter, and the fire linkage controller in the fire control room shall be able to manually control the lowering of the fire shutter.
说明:非疏散通道上设置的防火卷帘大多仅用于建筑的防火分隔作用,建筑共享大厅回廊楼层间等处设置的防火卷帘不具有疏散功能,仅用作防火分隔。因此,设置在防火卷帘所在防火分区内的两只独立的火灾探测器的报警信号即可联动控制防火卷帘一步降到楼板面。
Note: Most of the fire rolling shutters set on non evacuation corridors are only used for fire separation of buildings. The fire rolling shutters set between floors in the corridors of the building sharing hall do not have evacuation functions and are only used for fire separation. Therefore, the alarm signals of two independent fire detectors set in the fire compartment where the fire shutter is located can be linked to control the fire shutter to descend to the floor in one step.
4.防火卷帘下降距楼板面1.8m处、下降到楼板面的动作信号和防火卷帘控制器直接连接的感烟、感温火灾探测器的报警信号,应反馈消防联动控制器。
4. The action signal of the fire shutter descending to 1.8m from the floor and the alarm signal of the smoke and temperature detectors directly connected to the fire shutter controller shall be fed back to the fire linkage controller.
防火卷帘门起到防火、隔火作用,产品外形平整美观、造型新颖,具有钢性强的特点,在很多场景中都有所应用,您对此有需求可以随时来网站咨询联系我们http://xl0475.com
The fireproof rolling shutter door plays the role of fire prevention and fire separation. The product is flat and beautiful in appearance, novel in shape and strong in rigidity. It has been used in many scenes. You can contact us at any time if you need it http://xl0475.com !

阅读/ Recommended reading

快盈11v  检查电池 :  Check the battery:  检查遥控器电池是否还有电。如果电池电量不足,更换一节新的电池即可。在更换电池时,注意电池的正负极方向,确保放入的电池...

电动卷帘门的优势 2024-11-12
济南卷帘门:卷帘门遥控器失灵怎么办? 2024-09-02
济南卷帘门厂:卷帘门卡主了怎么办 2024-08-28
济南电动卷帘门:电动卷闸门没电了怎么开? 2024-08-28
济南卷帘门:控制器的安装技巧 2024-07-06
车库门出现故障怎么办? 2024-06-12
防火卷帘门分几种类别? 2024-06-06
防火卷帘门对于企业的使用有哪些? 2024-06-09