联系我们
快盈11v
联系人:林经理
电话:151 6888 2846
邮箱:527800164@qq.com
地址:济南市历下区化纤厂路8号3号楼101号
防火卷帘调试要注意什么?
来源:http://xl0475.com 日期:2023-09-20 发布人:
1、防火卷帘控制器应进行通电功能、备用电源、火灾报警功能、故障报警功能、自动控制功能、手动控制功能和自重下降功能调试,并应符合下列要求:
1. The fire shutter controller should be debugged for power on function, backup power supply, fire alarm function, fault alarm function, automatic control function, manual control function, and self weight lowering function, and should meet the following requirements:
(1)通电功能调试时,应将防火卷帘控制器分别与消防控制室的火灾报警控制器或消防联动控制设备、相关的火灾探测器、卷门机等连接并通电,防火卷帘控制器应处于正常工作状态。
(1) When debugging the power on function, the fire shutter controller should be connected and powered on to the fire alarm controller or fire linkage control equipment in the fire control room, relevant fire detectors, door rolling machines, etc. The fire shutter controller should be in normal working state.
检查数量:全数检查。
Inspection quantity: All inspections.
检查方法:直观检查。
Inspection method: Visual inspection.
(2)备用电源调试时,设有备用电源的防火卷帘,其控制器应有主、备电源转换功能。主、备电源的工作状态应有指示,主、备电源的转换不应使防火卷帘控制器发生误动作。备用电源的电池容量应保证防火卷帘控制器在备用电源供电条件下能正常可靠工作1h,并应提供控制器控制卷门机速放控制装置完成卷帘自重垂降,控制卷帘降下限位所需的电源。
(2) When debugging the backup power supply, the controller of the fire resistant roller shutter equipped with the backup power supply should have the function of switching between the main and backup power supplies. The working status of the main and backup power supplies should be indicated, and the conversion of the main and backup power supplies should not cause the fire shutter controller to malfunction. The battery capacity of the backup power supply should ensure that the fire resistant roller shutter controller can operate normally and reliably for 1 hour under the backup power supply conditions, and the controller should be provided to control the speed release control device of the roller shutter machine to complete the weight drop of the roller shutter and control the power supply required to lower the roller shutter to the lower limit.
检查数量:全数检查。
Inspection quantity: All inspections.
检查方法:切断防火卷帘控制器的主电源,观察电源工作指示灯变化情况和防火卷帘是否发生误动作。再切断卷门机主电源,使用备用电源供电,使防火卷帘控制器工作1h,用备用电源启动速放控制装置,观察防火卷帘动作、运行情况。
Inspection method: Cut off the main power supply of the fireproof roller shutter controller, observe the changes in the power indicator light and whether the fireproof roller shutter has malfunctioned. Cut off the main power supply of the rolling door machine again, use a backup power supply to power the fire shutter controller for 1 hour, start the quick release control device with the backup power supply, and observe the action and operation of the fire shutter.
(3)火灾报警功能调试时,防火卷帘控制器应直接或间接地接收来自火灾探测器组发出的火灾报警信号,并应发出声、光报警信号。
(3) When debugging the fire alarm function, the fire shutter controller should directly or indirectly receive the fire alarm signal from the fire detector group, and should emit sound and light alarm signals.
检查数量:全数检查。
Inspection quantity: All inspections.
检查方法:使火灾探测器组发出火灾报警信号,观察防火卷帘控制器的声、光报警情况。
Inspection method: Make the fire detector group emit a fire alarm signal, and observe the sound and light alarm of the fire shutter controller.
(4)故障报警功能调试时,防火卷帘控制器的电源缺相或相序有误,以及防火卷帘控制器与火灾探测器之间的连接线断线或发生故障,防火卷帘控制器均应发出故障报警信号。
(4) When debugging the fault alarm function, if the power supply of the fire shutter controller is out of phase or has incorrect phase sequence, as well as the connection line between the fire shutter controller and the fire detector is broken or malfunctioning, the fire shutter controller should send a fault alarm signal.
检查数量:全数检查。
Inspection quantity: All inspections.
检查方法:任意断开电源一相或对调电源的任意两相,手动操作防火卷帘控制器按钮,观察防火卷帘动作情况及防火卷帘控制器报警情况。断开火灾探测器与防火卷帘控制器的连接线,观察防火卷帘控制器报警情况。
Inspection method: Disconnect one phase of the power supply or switch between any two phases of the power supply, manually operate the button of the fire shutter controller, observe the action of the fire shutter and the alarm of the fire shutter controller. Disconnect the connection wire between the fire detector and the fire shutter controller, and observe the alarm status of the fire shutter controller.
(5)自动控制功能调试时,当防火卷帘控制器接收到火灾报警信号后,应输出控制防火卷帘完成相应动作的信号,并应符合下列要求:
(5) When debugging the automatic control function, when the fire shutter controller receives a fire alarm signal, it should output a signal to control the fire shutter to complete the corresponding action and meet the following requirements:
1)控制分隔防火分区的防火卷帘由上限位自动关闭全闭。
1) The fire roller shutter that controls the partition of the fire compartment automatically closes from the upper limit to the fully closed position.
2)防火卷帘控制器接到感烟火灾探测器的报警信号后,控制防火卷帘自动关闭中位(1.8m)处停止,接到感温火灾探测器的报警信号后,继续关闭全闭。
2) After receiving the alarm signal from the smoke fire detector, the fire shutter controller automatically closes to the middle position (1.8m) and stops. After receiving the alarm signal from the temperature fire detector, it continues to close until fully closed.
3)防火卷帘半降、全降的动作状态信号应反馈到消防控制室。
3) The action status signals of the fire shutter's half down and full down should be fed back to the fire control room.
检查数量:全数检查。
Inspection quantity: All inspections.
检查方法:分别使火灾探测器组发出半阵、全降信号,观察防火卷帘控制器声、光报警和防火卷帘动作、运行情况以及消防控制室防火卷帘动作状态信号显示情况。
Inspection method: Make the fire detector group emit half array and full down signals respectively, observe the sound and light alarms of the fire roller shutter controller, the action and operation of the fire roller shutter, and the display of the fire roller shutter action status signal in the fire control room.
(6)手动控制功能调试时,手动操作防火卷帘控制器上的按钮和手动按钮盒上的按钮,可控制防火卷帘的上升、下降、停止。
(6) When debugging the manual control function, manually operate the buttons on the fire shutter controller and the buttons on the manual button box to control the rise, fall, and stop of the fire shutter.
检查数量:全数检查。
Inspection quantity: All inspections.
检查方法:手动试验。
Inspection method: manual test.
(7)自重下降功能调试时,应将卷门机电源设置于故障状态,防火卷帘应在防火卷帘控制器的控制下,依靠自重下降全闭。
(7) When debugging the self weight lowering function, the power supply of the rolling door machine should be set to a fault state, and the fire shutter should be controlled by the fire shutter controller to lower to fully closed by relying on its self weight.
检查数量:全数检查。
Inspection quantity: All inspections.
检查方法:切断卷门机电源,按下防火卷帘控制器下降按钮,观察防火卷帘动作、运行情况。
Inspection method: Cut off the power supply of the rolling door machine, press the down button of the fire shutter controller, and observe the action and operation of the fire shutter.
感谢您的阅读,此文的文章来源:济南卷帘门更多的内容和问题请点 http://xl0475.com我们会继续努力的为您提供服务,感谢您的支持!
Thank you for reading. The source of this article is Jinan Rolling Shutter Doors. For more information and questions, please click http://xl0475.com We will continue to work hard to provide you with services. Thank you for your support!
下一篇:电动卷闸门故障及维修要注意什么? 上一篇:电动卷帘门的12个小故障排除技巧
阅读/ Recommended reading
- 重视卷帘门门口堆物问题 2024-11-06
- 快速卷帘门介绍与快速卷帘门材料说明 2024-10-26
- 济南卷帘门厂:卷帘门安装施工工艺详解 2024-10-14
- 济南卷帘门安装秘籍,让家居更有面子 2024-09-21
- 济南遥控卷帘门:我来教你——卷闸门遥控器遇到故障怎么办? 2024-08-28
- 济南卷帘门:卷帘门(不锈钢款) 2024-07-25
- 济南卷帘门的故障维修与更换卷帘门注意事项 2024-07-19
- 选错济南卷帘门的后果居然有这么严重? 2024-07-13
如何延长卷闸门的寿命
2024-11-06
铝合金原料的卷帘门日常保养影响着其运用寿命,下面在教你10个诀窍,保证电动卷帘门在运用过程中更顺利,运用寿命更长。 The daily maintenance of alum...